TTI series is made of transformers whose primary and secondary coils are electrically separated through ane lectrostatic screen in order to reduce any danger due to a simultaneous accidental contact between earth and metallic parts that could go under tension in case of a breakdown of the insulation.
The connection of phases is usually possible as star. In request the dimensions can be changed in order to fulfil any volume requirement.
Technical specifications: |
– insulation class E – frequency 50/60 Hz. – open execution, protection level IP00 – ambient temperature 40°C – either vertical or horizontal execution – resin impregnated and tropicalised – vectorial group Yy0 – other vectorial groups on request – electric class of protection l – screen between primary and secondary |
|
Essential information for order and offers inquiries: |
– power in VA or in KVA – network tension and frequency – output tension – connection type – ambient temperature – working ambient conditions – quantity of screens to be fitted |
Primary Tension: | 230-400Vac |
Secondary Tension: | 230Vac+N (accessibile) oppure 400Vac+N (accessibile) |
Final code: | 230+N=Cod.2 / 400+N=Cod.4 |
Code | Power Va |
Watt loss Watt |
Dv % |
Vcc % |
Dim. A |
Dim. B |
Dim. C |
Dim. D |
Dim. E |
Weight Kg |
TTI030- | 300 | 30 | 3,5 | 3,7 | 170 | 180 | 120 | 150 | 70 | 8,5 |
TTI050- | 500 | 45 | 3,4 | 3.6 | 170 | 180 | 140 | 150 | 90 | 12,5 |
TTI10- | 1000 | 98 | 4,9 | 7,1 | 230 | 240 | 150 | 200 | 80 | 17 |
TTI100- | 10000 | 540 | 3,8 | 5 | 420 | 420 | 240 | 375 | 140 | 92 |
TTI15- | 1500 | 120 | 4,4 | 5,9 | 250 | 240 | 170 | 200 | 100 | 20,5 |
TTI150- | 15000 | 780 | 3,8 | 5,1 | 420 | 420 | 260 | 375 | 160 | 113 |
TTI20- | 2000 | 150 | 4,2 | 5,5 | 300 | 300 | 180 | 250 | 110 | 28,5 |
TTI200- | 20000 | 920 | 3,6 | 74,8 | 490 | 480 | 270 | 455 | 140 | 135 |
TTI25- | 2500 | 160 | 4 | 5 | 300 | 300 | 190 | 250 | 110 | 35 |
TTI250- | 25000 | 995 | 3,6 | 4,8 | 490 | 480 | 290 | 455 | 160 | 162 |
TTI300- | 30000 | 1200 | 3,5 | 4,5 | 490 | 480 | 310 | 455 | 180 | 190 |
TTI40- | 4000 | 190 | 4 | 5 | 300 | 300 | 210 | 250 | 1230 | 46 |
TTI400- | 40000 | 1400 | 3,5 | 4,5 | 620 | 620 | 330 | 455 | 160 | 238 |
TTI50- | 5000 | 330 | 4 | 5,2 | 360 | 360 | 220 | 325 | 150 | 73 |
TTI75- | 7500 | 400 | 4 | 5 | 360 | 360 | 230 | 325 | 150 | 83 |
Dv: tension drop from vacuum to full load – Vcc: short-circuit tension. |