TTs series transformers are meant to supply very low tension circuits. The secondary nominal tension and the vacuum secondary tension must not exceed 50V. The constructional specifications are identical to the normal trasnformers with the exception of ahaving: reinforced insulation, an increased insulation distance and the possibility of having an extra antistatic screen between primary and secondary.
On request the dimensions can be changed in order to fulfil any volume requirement.

Technical specifications:
– insulation class E
– frequency 50/60 Hz.
– open execution, protection level IP00
– ambient temperature 40°C
– either vertical or horizontal execution
– resin impregnated and tropicalised
– vectorial group Yy0
– other vectorial groups on request
– electric class of protection l

Essential information for order and offers inquiries:
– power in VA or in KVA
– network tension and frequency
– output tension
– ambient temperature
– working ambient conditions
Primary Tension: 230-400Vac+N (accessibile)
Secondary Tension: 50Vac
Final code: Esempio : Trasformatore trifase da 1000VA P. 230-400Vac S.50Vac = TTS10
Code Power
Va
Watt loss
Watt
Dv
%
Vcc
%
Dim.
A
Dim.
B
Dim.
C
Dim.
D
Dim.
E
Weight
Kg
TTS030 300 31 5 8 170 180 120 150 70 9,5
TTS050 500 70 5 8 170 180 140 150 90 12
TTS10 1000 98 4,9 7,1 230 240 150 2000 80 17
TTS100 10000 540 3,9 4,9 410 420 240 375 142 92
TTS150 15000 700 2,8 4,9 410 420 260 375 162 110
TTS16 1600 120 4,6 6,1 250 240 170 200 100 20,5
TTS25 2500 160 4,1 5,1 300 300 190 250 110 34
TTS40 4000 190 4,1 5,1 300 300 210 250 130 46
TTS50 5000 330 4,1 5,1 360 360 220 325 150 73
Dv: tension drop from vacuum to full load – Vcc: short-circuit tension.